Detail publikace

Mathematical modelling and model validation of the heat losses in district heating networks

Jakubek, D., Ocłoń, P., Nowak-Ocłoń, M., Sułowicz, M., Varbanov, P. S., Klemeš, J. J.

Originální název

Mathematical modelling and model validation of the heat losses in district heating networks

Typ

článek v časopise ve Web of Science, Jimp

Jazyk

angličtina

Originální abstrakt

Today the most popular system of district heating systems is based on pre-insulated pipes arranged in parallel or twin-pipe configuration. One of the greatest difficulties with heat distribution through pipelines is thermal loss from the distribution. The most efficient solution to that problem is optimising the insulation wall thickness layer according to the pipe diameter. Heat losses should be minimised at a relatively low investment cost to find the most suitable insulation thickness economically. Numerous studies focus on analytical (1D model) calculations and numerical simulations. However, there is a research gap related to laboratory devices that allow measuring the operation parameters (fluid flow, the temperature of the fluid in the supply pipe and the return pipe). This paper presents an analysis of the heat losses from pre-insulated pipes and twin pipes in the heating system network. This study compares the heat losses in the ground calculated by analytical solution (1D model) with the measurements on the dedicated experimental setup. The calculations have been made for several heating network pipe variants: twin pipes: DN40, DN50, DN65, and their counterparts in a single parallel pre-insulated system. The insulation thickness used in all cases is 30.85 mm for DN40 and 32.00 mm for DN50 and DN65. The insulation is made of rigid polyurethane foam that meets the requirements of the PN-EN 253 standard. During the investigation, the thermal conductivity of insulation material is examined. The obtained thermal conductivity results are used in the calculations. The results from laboratory devices and analytical models have been compared, demonstrating good agreement – with a low error level in the range of approximately 8%, depending on the type of district heating pipe. The validated mathematical model of the heating network is then used to calculate the heat losses in a heating network connecting an underground storage tank with a ground source heat pump. The economic analysis shows that after 5 y, a return on investment is expected when comparing twin-pipe systems and single-pipe pre-insulated heating networks.

Klíčová slova

Heat transfer, District heating network, Heat losses

Autoři

Jakubek, D., Ocłoń, P., Nowak-Ocłoń, M., Sułowicz, M., Varbanov, P. S., Klemeš, J. J.

Vydáno

15. 3. 2023

ISSN

0360-5442

Periodikum

Energy

Ročník

267

Číslo

126460

Stát

Spojené království Velké Británie a Severního Irska

Strany od

1

Strany do

14

Strany počet

4

URL

BibTex

@article{BUT180501,
  author="Petar Sabev {Varbanov} and Jiří {Klemeš}",
  title="Mathematical modelling and model validation of the heat losses in district heating networks",
  journal="Energy",
  year="2023",
  volume="267",
  number="126460",
  pages="1--14",
  doi="10.1016/j.energy.2022.126460",
  issn="0360-5442",
  url="https://www.sciencedirect.com/science/article/pii/S0360544222033461#kwrds0010"
}