POSPÍŠIL, J.; ŠPILÁČEK, M.; KUDELA, L.
Originální název
Potential of Predictive Control for Improvement of Seasonal Coefficient of Performance of Air Source Heat Pump in Central European Climate Zone
Anglický název
Druh
Článek WoS
Originální abstrakt
This paper compares different operation models of the air-to-water heat pump (HP). Detail focus of this study aims at a potential to increase seasonal coefficient of performance (SCOP) by utilising the predictive control. The considered predictive control uses an outdoor air temperature forecast for the upcoming 48 h. The predictive control operates the heat pump so that it runs, preferably, during the periods of the day with the highest air temperature. For a detailed assessment, a model of the heat supply system with a heat pump supplemented by a heat accumulator has been developed. The mathematical model involves detailed algorithm for time-dependent quantification of the heat demand for the considered model building. Dataset of real operation tests of the HP helps correctly evaluate the coefficient of performance (COP). An original algorithm of predictive control has been developed and tested for different operating parameters and different capacities of the heat accumulator. A long-term record of air temperatures from the last ten years is employed to evaluate the model. The mathematical model allows for a complex parametrical study to evaluate the relations of SCOP - accumulator capacity, SCOP - method of heat pump control.
Anglický abstrakt
Klíčová slova
COP, heat pump, air-to-water, predictive control, heat source
Klíčová slova v angličtině
Autoři
Rok RIV
2019
Vydáno
01.07.2018
Nakladatel
Elsevier Ltd.
Místo
Duxford, Cambridge CB22 4QH, UK
ISSN
1873-6785
Periodikum
Energy
Svazek
154
Číslo
1
Stát
Spojené království Velké Británie a Severního Irska
Strany od
415
Strany do
423
Strany počet
9
URL
https://www.sciencedirect.com/science/article/pii/S0360544218307448
BibTex
@article{BUT147338, author="Jiří {Pospíšil} and Michal {Špiláček} and Libor {Kudela}", title="Potential of Predictive Control for Improvement of Seasonal Coefficient of Performance of Air Source Heat Pump in Central European Climate Zone", journal="Energy", year="2018", volume="154", number="1", pages="415--423", doi="10.1016/j.energy.2018.04.131", issn="0360-5442", url="https://www.sciencedirect.com/science/article/pii/S0360544218307448" }