Detail publikačního výsledku

Emission assessment of single-phase switch-mode PFC loads up to 150 kHz: Experimental analysis and modelling

COLLIN, A.; DRÁPELA, J.; LANGELLA, R.; TESTA, A.

Originální název

Emission assessment of single-phase switch-mode PFC loads up to 150 kHz: Experimental analysis and modelling

Anglický název

Emission assessment of single-phase switch-mode PFC loads up to 150 kHz: Experimental analysis and modelling

Druh

Článek WoS

Originální abstrakt

The ongoing integration of new power electronic interfaces is increasing emissions in the frequency range between 2 and 150 kHz. This paper considers the emission assessment from 0 to 150 kHz of the switch-mode power factor correction converter topologies widely utilised in modern single-phase loads. First, experimental analysis of a load constituted by a variable switching frequency converter is performed to introduce modelling considerations and proposals for the extended frequency range. Then, a full circuit time domain model of the considered load is developed. Following this, a fast and accurate hybrid modelling technique which simultaneously models the low frequency (f < 2 kHz) and high frequency (2 <= f < 150 kHz) emissions is presented. The proposed hybrid technique can be readily applied to a range of topologies and control algorithms and easily integrated in Iterative Harmonic Analysis for system level analysis of distortion up to 150 kHz.

Anglický abstrakt

The ongoing integration of new power electronic interfaces is increasing emissions in the frequency range between 2 and 150 kHz. This paper considers the emission assessment from 0 to 150 kHz of the switch-mode power factor correction converter topologies widely utilised in modern single-phase loads. First, experimental analysis of a load constituted by a variable switching frequency converter is performed to introduce modelling considerations and proposals for the extended frequency range. Then, a full circuit time domain model of the considered load is developed. Following this, a fast and accurate hybrid modelling technique which simultaneously models the low frequency (f < 2 kHz) and high frequency (2 <= f < 150 kHz) emissions is presented. The proposed hybrid technique can be readily applied to a range of topologies and control algorithms and easily integrated in Iterative Harmonic Analysis for system level analysis of distortion up to 150 kHz.

Klíčová slova

Ac-dc power converters; Load modelling; Low and high frequency emissions; Power quality; Power system harmonics

Klíčová slova v angličtině

Ac-dc power converters; Load modelling; Low and high frequency emissions; Power quality; Power system harmonics

Autoři

COLLIN, A.; DRÁPELA, J.; LANGELLA, R.; TESTA, A.

Rok RIV

2024

Vydáno

15.07.2023

Nakladatel

Elsevier

Místo

LAUSANNE

ISSN

0378-7796

Periodikum

ELECTRIC POWER SYSTEMS RESEARCH

Svazek

220

Číslo

1

Stát

Švýcarská konfederace

Strany od

1

Strany do

9

Strany počet

9

URL

Plný text v Digitální knihovně

BibTex

@article{BUT182822,
  author="Adam {Collin} and Jiří {Drápela} and Roberto {Langella} and Alfredo {Testa}",
  title="Emission assessment of single-phase switch-mode PFC loads up to 150 kHz: Experimental analysis and modelling",
  journal="ELECTRIC POWER SYSTEMS RESEARCH",
  year="2023",
  volume="220",
  number="1",
  pages="1--9",
  doi="10.1016/j.epsr.2023.109236",
  issn="0378-7796",
  url="https://www.sciencedirect.com/science/article/pii/S0378779623001256"
}