Originální abstrakt
Resilience assessment is also relevant for highly reliable power systems, such as meshed networks. The paper deals with resilience of an urban dense‐meshed low voltage network to supply feeder outages and subsequent cascading failures. Presented resilience analysis evaluates the amount of preserved load during multiple feeder outages. The simulations account for a time‐span of 1 year of network operation with regard to load variations. Based on disturbances simulation results, the weakest elements of the network are identified. To increase resilience, corrective measures are proposed and incorporated into the simulations. Resilience improvements of applied measures are evaluated and discussed.
Anglický abstrakt
Klíčová slova
meshed network; cascading failure; resilience; distribution network; low voltage; feeder outage
Klíčová slova v angličtině
Autoři
Rok RIV
2026
Vydáno
08.10.2025
Periodikum
IET Generation Transmission & Distribution
Svazek
19
Číslo
1
Stát
Spojené království Velké Británie a Severního Irska
Strany od
Strany do
11
Strany počet
URL
https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/gtd2.70157
Plný text v Digitální knihovně
http://hdl.handle.net/11012/255589
BibTex
@article{BUT198765, author="Vít {Krčál} and Jan {Koudelka} and Matěj {Vrtal} and David {Topolánek} and Petr {Toman}", title="Resilience Analysis of Extensive Meshed Distribution Network to Supply Feeder Outages", journal="IET Generation Transmission & Distribution", year="2025", volume="19", number="1", pages="1--11", doi="10.1049/gtd2.70157", issn="1751-8687", url="https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/gtd2.70157" }