Publication result detail

Power Line Communication as a Sensor: Medium Voltage Cable Diagnostics

BENEŠL, L.; MLÝNEK, P.; KRBAL, M.; RUSZ, M.; MUSIL, P.; MIŠUREC, J.; SLÁČIK, J.

Original Title

Power Line Communication as a Sensor: Medium Voltage Cable Diagnostics

English Title

Power Line Communication as a Sensor: Medium Voltage Cable Diagnostics

Type

WoS Article

Original Abstract

This article explores the secondary use of power line communication (PLC) technology, specifically broadband power line (BPL), as a diagnostic tool for medium voltage (MV) cable lines. Through experimental measurements, it was confirmed that selected communication parameters of BPL modems exhibit measurable deviations in the presence of partial discharge (PD) activity. Specifically, the parameters considered are throughput, signal-to-noise ratio (SNR), link capacity, bit load estimate (BLE), transmission amplitude map, Tonemap (modulation scheme), and Tonemask. In particular, BPL throughput decreased by approximately 10 Mbps for 100 pC PD and by around 50% for 1,000 pC PD. Since partial discharges are an early indicator of insulation system degradation, their detection supports predictive maintenance and contributes to improving the operational reliability of distribution networks. The results demonstrate that PLC/BPL technology–originally designed for communication and automation of distribution transformer stations (DTS)–can also serve as a cost-effective and readily deployable sensor system for real-time monitoring of cable health, without the need for dedicated diagnostic equipment. Experiments employing both inductive and capacitive couplers confirm the effectiveness of this secondary application in detecting insulation-related anomalies.

English abstract

This article explores the secondary use of power line communication (PLC) technology, specifically broadband power line (BPL), as a diagnostic tool for medium voltage (MV) cable lines. Through experimental measurements, it was confirmed that selected communication parameters of BPL modems exhibit measurable deviations in the presence of partial discharge (PD) activity. Specifically, the parameters considered are throughput, signal-to-noise ratio (SNR), link capacity, bit load estimate (BLE), transmission amplitude map, Tonemap (modulation scheme), and Tonemask. In particular, BPL throughput decreased by approximately 10 Mbps for 100 pC PD and by around 50% for 1,000 pC PD. Since partial discharges are an early indicator of insulation system degradation, their detection supports predictive maintenance and contributes to improving the operational reliability of distribution networks. The results demonstrate that PLC/BPL technology–originally designed for communication and automation of distribution transformer stations (DTS)–can also serve as a cost-effective and readily deployable sensor system for real-time monitoring of cable health, without the need for dedicated diagnostic equipment. Experiments employing both inductive and capacitive couplers confirm the effectiveness of this secondary application in detecting insulation-related anomalies.

Keywords

broadband power line (BPL) cable diagnostics capacitive coupler inductive coupler medium voltage cables partial discharge detection power line communication (PLC)

Key words in English

broadband power line (BPL) cable diagnostics capacitive coupler inductive coupler medium voltage cables partial discharge detection power line communication (PLC)

Authors

BENEŠL, L.; MLÝNEK, P.; KRBAL, M.; RUSZ, M.; MUSIL, P.; MIŠUREC, J.; SLÁČIK, J.

Released

05.02.2026

Publisher

WILEY

Periodical

IET Generation Transmission & Distribution

Volume

20

Number

1

State

United Kingdom of Great Britain and Northern Ireland

Pages from

1

Pages to

19

Pages count

19

URL

BibTex

@article{BUT201071,
  author="Lukáš {Benešl} and Petr {Mlýnek} and Michal {Krbal} and Martin {Rusz} and Petr {Musil} and Jiří {Mišurec} and Ján {Sláčik}",
  title="Power Line Communication as a Sensor: Medium Voltage Cable Diagnostics",
  journal="IET Generation Transmission & Distribution",
  year="2026",
  volume="20",
  number="1",
  pages="1--19",
  doi="10.1049/gtd2.70248",
  issn="1751-8687",
  url="https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/gtd2.70248"
}